A step-by-step guide for engineers
The integration of modern communication protocols into industrial control systems is becoming increasingly important. In this blog post we will show you how to SIMATIC PDM-Configure project to connect to isNet Lite + isNet H@rt Gateway to produce. These instructions are specifically aimed at engineers who deal with the setup and optimization of process automation systems.
Requirements
Before you start, please make sure:
- you access to isNet Lite have web interface.
- The HART can be activated via IP protocol.
- SIMATIC Manager is installed and ready for operation.
- The for SIMATIC PDM Required HART Server License is installed and activated.
Step-by-step instructions
1. HART over IP protocol activation
- web interface: Navigate to the appropriate IsNet Lite’s web interface
Settings and activate the HART over IP protocol.

2. Starting the HART Server

3. Network Configuration
Add network:
- Right-click on the hard server and choose “Add Network…”.
- Select TCP/UDP and click [Add].

- Enter a meaningful name for the gateway (e.g. ‘IsNetLite’) and confirm with [OK].

4. Adding the I/O System
Integrate I/O system:
- Right-click on the newly created entry ‘IsNetLite’ and
choose ‘Add I/O system’.

- Enter the correct IP address of the isNet Lite.
In the delivery state, this is 192.168.0.10.
- Change the port to 5094.
- Click [Add].

- Click [OK].


5. Tag Configuration
Tag attachment:
- After the I/O system has been added, enter a suitable one
enter tag name and confirm with [OK].
- Then right-click on the tag name and select ‘Learn‘.

- Confirm with [Yes] so that the Gateway Start scanning the connected HART transmitters.

6. Save project and extension in SIMATIC Manager
Save project:
Save your current project via File → Save.

Create a new project:
- Without shutting down the HART server, return to SIMATIC Manager back and create a new project.
- Right-click on ‘Networks“ and choose: Insert New Object → HART Server.



- With the right mouse button you have to SIMATIC PDM navigate to synchronize.



7. Device selection and access
Device configuration:
- SIMATIC PDM Opens a dialog, selecting all subset objects.
- synchronized after launch SIMATIC PDM himself with the HART server.
The green hooks indicate that the project is properly configured up to the HART device. - Confirm the [Close] button to end the dialog.



Conclusion
The establishment of a SIMATIC PDM project for operation with the isNet Lite + isNet H@rt Gateway can be implemented in an uncomplicated way if you proceed step by step. By carefully configuring and precisely tuning all elements (from activating the HART from IP protocols to device selection) Ensure that your system works efficiently and reliably.
If you have any questions or would like to delve deeper into certain aspects, we look forward to your feedback. What challenges have you encountered in integrating modern communication interfaces in your system? Feel free to share your experiences and discussions in the comments!